PASS-THROUGH MINIATURE CURRENT TRANSFORMERS
Overload: 1,2 In (permanent). Insulation class: E (0,72 kV dry, 3 kV for 1' at 50 Hz). Working temperature: -25+50 °C. Wall mount and DIN rail mount base. Accuracy: class 0,5 - 1 - 3 depending on burden applied. | - CTA 09 - Miniature current transformer, Ø18mm. pass through hole, flexible collar + tie fixing
- CTA 19 - Miniature current transformer, Ø32mm. pass through hole, flexible collar + tie fixing
- CTA 29 - Miniature current transformer, Ø52mm. pass through hole, flexible collar + tie fixing
|
PASS-THROUGH CURRENT TRANSFORMERS
Overload: 1,2 In (permanent). Insulation class: E (0,72 kV dry, 3 kV for 1' at 50 Hz). Working temperature: -25+50 °C. Wall mount and DIN rail mount base. Accuracy: class 0,5 - 1 - 3 depending on burden applied. | - CTA 09 - Miniature current transformer, Ø18mm. pass through hole, flexible collar + tie fixing
- CTA 11 - Current transformer, wall and DIN rail mount, size 60x92mm. Cable/bar size: Ø21mm.
- CTA 19 - Miniature current transformer, Ø32mm. pass through hole, flexible collar + tie fixing
- CTA 21 - Current transformer, wall and DIN rail mount, size 60x92mm. Cable/bar size: Ø23mm., 30x10mm
- CTA 29 - Miniature current transformer, Ø52mm. pass through hole, flexible collar + tie fixing
- CTA 31 - Current transformer, wall and DIN rail mount, size 73x102mm. Cable/bar size: Ø29mm., 40x10mm.
- CTA 41 - Current transformer,wall and DIN rail mount,size 100x128mm.Cable/bar size: 50mm.,80x10mm.,60x33mm
- CTA 51 - Current transformer, size 125x150mm. Cable/bar size: 82x40mm.
- CTA 58 - Current transformer, size 125x150mm. Cable/bar size: Ø80mm.
- CTA 61 - Current transformer, size 175x182mm. Cable/bar size: 128x54mm.
|
WOUND-PRIMARY CURRENT TRANSFORMERS
Overload: 1,2 In (permanent). Insulation class: E (0,72 kV dry, 3 kV for 1' at 50 Hz). Working temperature: -25 +50 °C. Wall mount and DIN rail mount base. Accuracy: class 0,5 - 1 - 3 depending on burden applied. | - CTA 0 - Current transformer, wall and DIN rail mount, size 60x92mm.
Cage terminals suitable for conductors up to 10 mmq. - CTA 01 - Current transformer, wall and DIN rail mount, size 60x92mm.
Secondary cage terminals suitable for conductors up to 10 mmq. Primary connection with 10x3mm bar. - CTA 02 - Current transformer, wall and DIN rail mount, size 100x128mm.
Secondary cage terminals suitable for conductors up to 10 mmq. Primary connection with 35x3mm bar . - CTA 03 - Current transformer, wall and DIN rail mount, size 100x128mm.
Secondary cage terminals suitable for conductors up to 10 mmq. Primary connection with 35x3mm bar.
| |
PROTECTION CURRENT TRANSFORMERS
Overload: 1,2 In (permanent). Insulation class: E (1,2 kV dry, 6 kV for 1' at 50 Hz). Working temperature: -25 +50 °C. Wall mount and DIN rail mount base. Accuracy: Class 5P10, 5P15. Class 5P20 available on request. | - CTA 51/O - Protection current transformer, size 125x150mm. Cable/bar size: Ø80mm.
- CTA 03 - Protection current transformer, wall and DIN rail mount, size 100x128x160mm.
Secondary cage terminals suitable for conductors up to 10 mmq. Primary connection with 35x3mm bar.. - CTA 04 - Protection current transformer, wall and DIN rail mount, size 100x128x184mm.
Secondary cage terminals suitable for conductors up to 10 mmq. Primary connection with 35x3mm bar.
| |
SUMMATING CURRENT TRANSFORMERS
It delivers the vectorial summation of the currents of two or more lines belonging to same grid. Overload: 1,2 In (permanent). Insulation class: E (0,72 kV dry, 3 kV for 1' at 50 Hz). Working temperature: -25 +50 °C. Wall mount and DIN rail mount base. Accuracy: Cl. 0,5 | - CTA 92 - Summating current transformer, size 100x128mm, 10 mmq cage terminals.
|
VOLTAGE TRANSFORMERS
Insulation class: E (1,2 kV dry, 6 kV for 1' at 50 Hz). Working temperature: -25 +50 °C. Wall mount and DIN rail mount base. Accuracy: cl. 1. Standard secondary voltages: 100V, 100:√3, 110V, 110:√3 | - CTV 10 - Voltage transformer, size 100x128mm. 10 mmq cage terminals.
|
|